Other Alarms Configuration Sub-Menu
Parameter
Factory
Lo Load
Enable Lo Load
Hi Load
Disable
Hi Load
*n/a (30.0A)
Hi Load Filter
*n/a (0 sec)
Hi GFI
Enable
Hi GFI
20 mA
Hi GFI Filter
0 sec
GFI Trip
Enable
GFI Trip
30 mA
Lo Volt
Enable
Lo Volt
90 V
Lo Volt Filter
0 sec
Hi Volt
Disable
Hi Volt
*n/a (270V)
Hi Volt Filter
*n/a (0 sec)
Lo Resist
Disable
Lo Resist
*n/a (50%)
Lo Resist Filter
*n/a (0 sec)
Hi Resist
Disable
Hi Resist
*n/a (50%)
Hi Resist Filter
*n/a (0 sec)
Nominal Resist
*n/a (6.00 Ω)
Overcurrent Trip
*n/a (Enable)
Switch Fail
Enable
HTC Reset
Disable
C.B. Limiting
*n/a (Disable)
Power Limiting
*n/a (Disable)
Switch Limiting
*n/a (Disable)
Contactor Count
Enable
Contactor Count
200,000
EEROM Data Fail
Enable
User
1.0 A Lo Load Filter
0 sec