nvent 910 Series Installation, Operating And Maintenance Instructions page 24

Table of Contents

Advertisement

24 | nVent.com
4.3.6 "MISC. SETUP..." SUB-MENU
The "Misc. Setup" sub-menu is used to configure miscellaneous parameters.
CONTROL SETPOINT = 20°C
LO TS 1 = –10°C
LO LOAD = 1.0 A
HI GFI = 50 mA
GFI TRIP = 75 mA
TS ALARMS CONFIG...
OTHER ALARMS CONFIG...
POINT SETUP...
MISC SETUP...
COMMUNICATIONS SETUP...
---- END ----
Table 4.9 Misc. Setup Sub-Menu
TEMP UNITS
VERSION
EXT. INPUT
FLASH ALARM OUTPUT
ALARM OUTPUT
LANGUAGE
PASSCODE
SCROLL DELAY
LOAD DEFAULTS
---- END ----
=
{°C or °F}
=
V3.16.3
=
{NOT USED, INHIBIT or FORCE ON}
=
{YES or NO}
=
{N.C. or N.O.}
=
{ENGLISH or FRANCAIS}
=
{0000 to 9999}
(only if 0 or database is unlocked)
=
{0.07 to 0.25} S