Sensor installation

6.2.2 Installation in pipe

Depending on process connections, the sensor is connected to the pipe by means of
flanges, terminals or thread. The MS code provides information on the process
connections selected.
Risk of injury due to escaping fluids and damage, if fixing materials are in-
DANGER
appropriate or not professionally installed
▶ Fixing materials (screws, nuts, terminals, terminal connectors, gaskets, etc.) are not
Clamp connection
The clamp connection must be installed as shown in the figure below.
Fig. 10: Clamp connection
1
2
3
included in the delivery and must be provided by the customer. The operator is re-
sponsible for selecting suitable gaskets and defining corresponding torque values.
Protective materials such as protective stickers or caps on process connections must
be removed immediately before installation.
The direction in which the medium flows through the pipe is indicated by an arrow on
the flow meter. The sensor must be installed in accordance with the flow direction in-
dicated to ensure optimal measuring results for density measurements.
Otherwise, the parameter flow direction in the transmitter menu must be changed,
see applicable software instruction manual.
Terminal
Gasket
Terminal connector
IM01U10A00-00EN-R, 2nd edition, 2017-08-29