Sensor Installation; General Installation Rules - YOKOGAWA Total Insight series Quick Reference Instruction Manual

Total insight coriolis mass flow and density meter
Table of Contents

Advertisement

Quick Reference Instruction Manual
Installation

6.2 Sensor installation

6.2.1 General installation rules

Risk of injury due to escaping fluids, if pipe connection is faulty
DANGER
▶ Correct slope and mismatch of pipe connections before inserting the sensor.
Fig. 8: Avoid: Slope and mismatch
Fig. 9: Installation to be avoided: Fixing the sensor
1
2
Avoiding creation of noise
Zero point stability is a prerequisite for exact mass flow measurement. Insufficient instal-
lation may lead to mechanical tensions or flow noise which impact zero point stability.
Countermeasures to help avoid noise creation:
16 / 54
Avoid fixing anything directly to the sensor. Doing so may result in increased devia-
tions.
1
1
2
Pipe
Sensor
Secure pipes before installing the flow meter.
Avoid damaging the process connections.
Flush new pipes before installing the flow meter to remove foreign matter, such as
shavings or other residues.
Support sensor weight by using soft coupling (silicone or other types of cushioning
materials).
Avoid bending or tensioning the sensor while aligning the pipe.
Avoid reductions or expansions in pipe directly up- or downstream of flow meter.
Avoid placing control valves, apertures or other devices generating noise near the
sensor.