Technical Specifications; Analog Inputs; Digital Inputs - Emerson iPro.Genius Installation And Operational Manual

Discharge air controller
Table of Contents

Advertisement

9.3. Technical Specifications

9.3.1. Analog Inputs

Analog conversion
10-bit A/D converter
type:
Number of inputs: 10
Type of analog
NTC Dixell (-50T110°C;
input:
10KΩ±1% at 25°C)
(configurable via
PTC Dixell (-55T115°C;
software
990Ω±1% at 25°C)
parameter)
Digital input (volt-free contact)
Voltage: 0 - V, 0 - 5V, 0 - 10V
(input resistance 3.7KΩ)
Current: 0 - 20mA, 4 - 20mA
(input resistance 100Ω)
Digital input status
250ms
variation detection
time:
Accuracy:
NTC, PTC: ±1?
0-1V: ±20mV
0-5V: ±100mV
0-10V:±200mV
2-20mA, 4-20mA: ±0.30mA
Additional power: +12V: 200mA in total
+5V: 100mA
Table 9-3 - Analog Input Specifications
CAUTION! Any inputs that are powered with
a voltage that differs from that supplied by the
device (+12V or +5V) must be powered
separately with another transformer (do not use the
same secondary of the controller's power) in order to
prevent the inputs from malfunctioning or being
damaged.
36 • Technical Specifications

9.3.2. Digital Inputs

Type:
Opto-insulated volt-free
(configurable via
External power 24VAC/DC
software
±20%
parameter)
Number of inputs: 20
Digital input status
250ms
variation detection
time:
Table 9-4 - Digital Input Specifications
CAUTION! If the digital inputs are used with
voltage, use another transformer (do not use
the same secondary of the controller's power)
in order to prevent the inputs from malfunctioning or
being damaged.
026-1727 Rev 3

Hide quick links:

Advertisement

Table of Contents
loading