Analog Outputs; Digital Outputs - Emerson iPro.Genius Installation And Operational Manual

Discharge air controller
Table of Contents

Advertisement

9.3.3. Analog Outputs

Type:
Opto-insulated with separate
24VAC/DC power supply
Number of out-
10
puts:
Type of analog
4 fixed outputs 0-10VDC (Out1
output:
- Out4)
2 configurable outputs 
(configurable via
0-10VDC, 
software
parameter)
4-20mA (Out5 and Out6)
Maximum load:
40mA (Out1 - Out4)
20mA (Out5 and Out6) max
with configured outputs 
0-10VDC
400Ω max with configured
outputs 4-20Ma
22Ω per live analog output
Accuracy:
Out1 - Out4: ±2% full scale
Out5 – Out6: ±2% full scale
Resolution:
8bit
Table 9-5 - Analog Outputs Specification
CAUTION! The electrical devices controlled
by these analog outputs must be powered sepa-
rately with another transformer (do not use the
same secondary of the controller's power) in order to
prevent the outputs from malfunctioning or being
damaged.
Discharge Air Controller (DAC) Manual

9.3.4. Digital Outputs

Type:
Relays with NO contacts
Number of
10 or 15, depending on the
outputs:
model
Type of output:
Relays with normally open
(configurable via
contact
software
parameter)
Maximum load:
5A(250VAC) SPST 5(2)A
Table 9-6 - Digital Outputs Specifications
CAUTION! Verify the capacity of the output
used. There is double insulation between the
digital outputs and the low voltage of the rest
of the circuit. Do not use different voltages for the
various groups of relays nor within each group.
Connections • 37