9.2. Terminal Number Descriptions

Terminal
Type of Input
No.
1
Supply
2
3
4
5
6
7
8
GND(-)
9
Supply
10
11
12
13
14
Pb10
15
16
+12V
21
Out1
22
Out2
23
Out3
24
Out4
25
GND(-)
26
Out5
27
Out6
28
Supply
29
Supply
30
GND(-)
40
41
42
43
44
45
46
Table 9-2 - Terminal Number Descriptions
Discharge Air Controller (DAC) Manual
Power 24VAC or 24VDC(-)
Pb1
Analog Input 1 (Temperature, 0-10V, 0-1V, 0-5V)
Pb2
Analog Input 2 (Temperature, 0-10V, 0-1V, 0-5V)
Pb3
Analog Input 3 (Temperature, 0-10V, 0-1V, 0-5V)
Pb4
Analog Input 4 (Temperature, 0-10V, 0-1V, 0-5V)
Pb5
Analog Input 5 (Temperature, 0-10V, 0-1V, 0-5V)
PbC
Common for temperature inputs (DO NOT TIE TO GROUND)
Additional power reference 5VDC and 12VDC and analog inputs (0 -10V, 
0 -1V, 0 -5V)
Power 24VAC or 24VDC(+)
Pb6
Analog Input 6 (Temperature, 0-10V, 0-1V, 0-5V)
Pb7
Analog Input 7 (Temperature, 0-10V, 0-1V, 0-5V)
Pb8
Analog Input 8 (Temperature, 0-10V, 0-1V, 0-5V)
Pb9
Analog Input 9 (Temperature, 0-10V, 0-1V, 0-5V)
Analog Input 10 (Temperature, 0-10V, 0-1V, 0-5V)
+5V
Additional power +5VDC
Additional power +12VDC
Opto-insulated analog output 1, 0-10V
Opto-insulated analog output 2, 0-10V
Opto-insulated analog output 3, 0-10V
Opto-insulated analog output 4, 0-10V
Common opto-insulated analog output
analog output 5, 0-10V
analog output 6, 0-10V
Power for opto-insulated analog outputs at 24VAC or 24VDC(-)
Power for opto-insulated analog outputs at 24VAC or 24VDC(+)
Common opto-insulated analog output
DI1
Opto-insulated digital input 1
DI2
Opto-insulated digital input 2
DI3
Opto-insulated digital input 3
DI4
Opto-insulated digital input 4
DI5
Opto-insulated digital input 5
DI6
Opto-insulated digital input 6
DI7
Opto-insulated digital input 7