Emerson iPro.Genius Installation And Operational Manual page 38

Discharge air controller
Table of Contents

Advertisement

iProDAC001.
Network Summary Screen
Figure 8-4 -
6. By default, each DAC's board number in the
network list is indicated by a - (dash). To set the
address and begin communication, press
Commission. (If you have more than one MODBUS
network, specify which network you want the
device to belong to.)
Specify MODBUS Address
Figure 8-5 -
7. After choosing the MODBUS network (if
applicable), press Enter and a screen will open that
30 • Add and Connect DACs
allows you set the address:.
Figure 8-6 - Set the Address of the DAC
8. When finished, press  to return to the Network
to
Setup menu, then press
Locate the DACs that you set up, and look at each
device's status in the Status field. You will see one
of the following messages:
• Online - The DAC is communicating normally.
• Offline - The DAC is not communicating, has not
been commissioned, is not functional, or is not
powered up. Verify the DAC is powered up, wired
correctly, and has the proper network address, baud
rate, and parity.
• Unknown - The DAC is not communicating or has
not been commissioned. Verify if the DAC is
powered up, wired correctly, and has the proper
network address, baud rate, and parity.
• No Port - No port is set up in the E2 Serial
Configuration Manager to be a MODBUS port.
• Wrong FW Rev - This message is likely caused by
the DAC having a firmware version older than the
minimum revision required by E2 for
communication. Replace the DAC with a new
controller that has the latest version of firmware on
- Network Summary.
026-1727 Rev 3