The Modbus Network; Wiring Types; Daisy Chains - Emerson iPro.Genius Installation And Operational Manual

Discharge air controller
Table of Contents

Advertisement

3

The MODBUS Network

Although the DAC can operate as a stand-alone
controller, it relies on an E2 unit for advanced features
such as remote dial-in/dial-out, logging, and alarm
control. The DAC uses an RS485 network connection
to communicate with E2 site controllers.

3.1. Wiring Types

Retail Solutions specs Belden #8761 shielded
twisted pair cables for use as MODBUS wiring (or
Belden #82761 and Belden #88761 for plenum
installations).
Figure 3-1 - MODBUS Networking
4 • Wiring Types
If the recommended cable is not available in your
area, be sure the wiring meets or exceeds the
following specs:
Shielded?
Conductor Type
Gauge
Capacitance between
signal wires
Capacitance between
signal and shield
Nominal Impedance

3.1.1. Daisy Chains

Connect the MODBUS network cable to the three-
terminal connector on the E2 COM port you wish to
assign as MODBUS. Reverse the polarity of +/- on
the RS485 cable between the E2 and the DAC.
Yes
Twisted Pair
18 - 24 AWG
31 pF/ft or less
(9.45 m) or less
59 pF/ft or less
(17.98 m) or less
12050
026-1727 Rev 3

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents