18. TECHNICAL SPECIFICATIONS

FEATURES
Housing
Dimensions
Mounting
Protection
Power Supply
Rated Power
Display
Terminal blocks
Environment
Operating Conditions
Storage Conditions
Resistance to Heat and Fire
Measurement range
Accuracy
Inputs
Relay Outputs
Real Time Clock
HOT KEY port
Approvals
1592040000 XR70T EN v1.1 2019.07.09
DESCRIPTION
Self-extinguishing PC
Front fascia 38x80 mm; case depth 81mm
Panel mounting, 71x29mm panel cut-out
Body: IP20; Front: IP66
230Vac 10%, 50/60Hz; 110Vac 10%, 50/60Hz; 100 to 240VAC10%, 50/60Hz; 12VAC 10%
Overvoltage category II
12VAC: 3VA; 110VAC: 4VA; 230VAC: 4VA; 100-240VAC: 3VA
White display, LED type, 3 digits with decimal point and multi-function icons
Plug-in or screw terminal block, wire section between 0,5 and 2,5 mm2
Max tightening force: 0.3 N/m for 3,5mm pitch, 0.4 N/m for 5,0mm pitch
Pollution degree 2, non-condensing humidity
IEC: 0T60°C; 20-85 rH% (non-condensing humidity)
UL: -20T60°C; 20-85 rH% (non-condensing humidity)
-25T60°C; 20-85 rH% (non-condensing humidity)
UL-V0
NTC: -40T110°C; resolution 0.1°C or 1°C (selectable)
PT1000: -100T150°C; resolution 0.1°C or 1°C (selectable)
PTC: -50T150°C; resolution 0.1°C or 1°C (selectable)
±1% compared to the full scale
Up to 4 NTC, PTC or PT1000 (configurable)
Up to 2 voltage free contacts
Nominal
SPST 16A,
oA1
250VAC
SPDT 8A,
oA2
250VAC
SPST 8A,
oA3
250VAC
SPST 5A,
oA4
250VAC
Action type 1B
Data maintenance up to 6 months with lithium battery
MAX voltage allowed is 5 VDC. DO NOT CONNECT ANY EXTERNAL POWER SUPPLY
R290/R600a: relays tested according to IEC EN60079:0 and IEC EN60079:15
IEC60730-2-9: 2008 (Third Edition) and Am.1:2011 in conjunction with IEC 60730-1:2010 (Fourth
Edition)
UL 60730-1, 5th edition, dated August 03, 2016
UL 60730-2-9, 4th edition, dated February 14, 2017
CAN/CSA-E60730-1, 5th edition, dated November 01, 2017
CAN/CSA-E60730-2-9:15 3rd edition, dated September, 2015
UL
10FLA, 60LRA, 30k cycles
Pilot Duty B300, 6k cycles
½ hp, 240 Vac, 30k cycles
Pilot Duty B300, 30k cycles
½ hp, 240 Vac, 30k cycles
Pilot Duty B300, 30k cycles
1.9FLA, 11.4LRA, 30k cycles
Pilot Duty B300, 30k cycles
XR70T
IEC
10(4)A, 250 Vac, 50-60 Hz,
100K cycles
8(3)A, 230 Vac, 50-60 Hz,
50K cycles
8(3)A, 230 Vac, 50-60 Hz,
50K cycles
5(1)A, 250 Vac, 50-60 Hz,
50K cycles
36/40