Table of Contents

Advertisement

4. Activating and configuring DeviceNet

4.
Activating and configuring DeviceNet
4.1

Activation of DeviceNet

The inserted DeviceNet module will be recognized automatically when the motor controller
is switched on. n order to activate, you must deactivate the CAN interface with DIP switch
11 at the CMMS/CMMD motor controller.
A unique MAC ID must be assigned to each device in the network. The MAC ID must be set
with DIP switches 1 ... 6 on the motor controller.
The baud rate must be set with DIP switches 9 and 10.
1 DIP switch 1 ... 6 (MAC-ID)
2 DIP switch 11
3 CAMC-DN slot
Fig. 4.1 DIP switch
DIP switch
Meaning
1
MAC ID.
See example
2
3
4
5
6
7
Reserved
8
Bootloader (If the switch is set to ON, the system searches for new firmware on the SD
card)
9
Transmission rate
Festo P.BE-CMMS-FHPP-DN-SW-EN en 1103a
1
2
3
15