7 Troubleshooting
Fault Code/Name
SE3
The output current was lower than 25% of
the motor no-load current during
Current Fault
operation.
The C2 sub-menu input terminal set for
SE4
"Brake Monitor NO" or "Brake Monitor
NC" did not respond within the Brake Flt
Brake Fdbk Flt
Time (A1) after an output terminal set for
"Brake Control" closed.
SvE
Position deviation during Position Lock.
Pos Lock Fault
STo
Motor pull out or step out has occurred.
Motor has exceeded its pull out torque.
PM Stall Flt
TrPC
IGBTs have reached 90% of their
expected performance life.
IGBT Alarm 2
The current has fallen below the
UL3
minimum value set for torque detection.
Should you need to adjust these factory
Undertorque 1
determined values, contact Magnetek for
Undertorq 1 Alm
more details.
The current has fallen below the
UL4
minimum value set for torque detection.
Should you need to adjust these factory
Undertorque 2
determined values, contact Magnetek for
Undertorq 2 Alm
more details.
62
Description
Causes and Solutions
The motor contactor is open.
• Check the contactor for any problems.
• Check for any sequencing problems between contact picking and the drive
being told to run.
The feedback contact on the brake is defective or the wiring is incorrect.
• Check the brake feedback contact and the wiring.
The brake control circuit does not work properly.
• Ensure the motor brake operates properly with a brake control command
from the drive.
Torque Limit is set too low.
• Set the torque limit to an appropriate value using Mtr Torque Limit (A1)
and Regen Torq Limit (A1).
Excessive load torque.
• Reduce the amount of load torque.
Noise interference along encoder wiring.
• Check the encoder signal for noise reference.
The wrong motor code has been set (only used for motor by drive
manufacturer).
• Enter the correct motor code for the PM being used into the A5 sub-menu.
• For special-purpose motors, enter the correct data to all parameters in the
A5 sub-menu according to the Test Report provided for the motor.
Load is too heavy.
• Reduce the load.
• Increase the motor or drive capacity.
Accel/decel ramp is too short.
• Lower the acceleration and deceleration in the A2 sub-menu.
• Lower the jerk setting in the A2 sub-menu.
IGBTs have reached 90% of their expected performance life.
• Replace the drive.
Parameter settings are not appropriate for the load.
• Check the settings of parameters.
There is a fault on the machine side.
• Check the load for any problems.
Parameter settings are not appropriate for the load.
• Check the settings of parameters.
There is a fault on the machine side.
• Check the load for any problems.
MAGNETEK HPV1000 AC Elevator Drive Technical Manual