Mounting Location - Siemens Pointek CLS200 Quick Start Manual

Digital. capacitance switches
Hide thumbs Also See for Pointek CLS200:

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1
• CLS200 pressure (vessel):
- rod version
- cable version
• CLS300 temperature
- rod/cable version
- high-temperature version -40 to +400 °C (-40 to +752 °F)
• CLS300 pressure (vessel):
Power
Bus voltage
• General purpose
• Intrinsically Safe
Installation
Notes:
• Installation shall only be performed by qualified personnel and in accordance with local
governing regulations.
• This product is susceptible to electrostatic shock. Follow proper grounding procedures.
• The housing may only be opened for maintenance, local operation, or electrical
installation.
• Before installing the instrument, verify that the environment complies with any restrictions
specified on the device nameplate.

Mounting Location

Notes:
• Keep the sensor at least 50 mm (2") away from any nozzle or tank wall.
• If multiple units are used, allow at least 100 mm (4") between them, to prevent interference
(mount diagonally if space is restricted).
• Do:
provide a sun shield to protect the transmitter from direct heat radiation.
• Do not:
exceed the permissible ambient temperature limits.
• Do not:
mount Pointek CLS200/300 in locations subject to strong vibrations (if it can be
avoided).
Pointek CLS200/300 (standard probe length): top or side mounting
vertical
normal process
level
High level alarm
• normally mounted into the vessel top, or
• through the tank wall at the detection level
1.
At process connection.
Page EN-4
Pointek CLS200/300 (Digital) – QUICK START MANUAL
-1 to 25 bar g/-14.6 to 365 psi g
-1 to 10 bar g/-14.6 to 150 psi g
1
:
-40 to +200 °C (-40 to +185 °F)
-1 to 35 bar g/-14.6 to 511 psi g
12 to 30 V DC, 12.5 mA
12 to 24 V DC, 12.5 mA
normal process
level
horizontal
7ML19985XA82