Safety clamp

If the galvanic isolation (PELV) between
control terminals and high-voltage termi-
nals is to be maintained, the accompany-
ing safety clamp must be fitted to VLT
Alternative fuses 380-500 V drives
VLT 2800
Bussmann
Bussmann
E52273
E4273
RK1/JDDZ
J/JDDZ
2805-
KTS-R20
JKS-20
2820
2855-
KTS-R25
JKS-25
2875
2880-
KTS-R50
JKS-50
2882
Alternative Fuses 200-240 V drives
VLT 2800
Bussmann
Bussmann
E52273
E4273
RK1/JDDZ
J/JDDZ
2803-2822
KTN-R20
JKS-20
2840
KTN-R25
JKS-25

Mains connection

Please note that at 1 x 220-240 Volt the neutral wire
must be attached to terminal N
must be connected to terminal L1
No. N
L1
Mains voltage 1 x 220-240 V
(L2)
(L1)
(L3)
N
L1
No.
95
Earth connection
No. N
L1
Mains voltage 3 x 220-240 V
(L2)
(L1)
(L3)
L2
L1
L3
No.
95
Earth connection
No. 91 92 93 Mains voltage 3 x 380-480 V
L1 L2 L3
No. 95
Earth connection
NB!
Please check that the mains voltage fits
the mains voltage of the frequency con-
®
MG.27.A2.02 - VLT
is a registered Danfoss trademark
Bussmann
Bussmann
Bussmann
E4273
E4273
E4273
T/JDDZ
CC/JDDZ
CC/JDDZ
JJS-20
FNQ-R-20
KTK-R-20
JJS-25
JJS-50
Bussmann
E4273
T/JDDZ
JJN-20
JJN-25
and the phase wire
(L2)
.
(L1)
®
VLT
2800 Series
2803-2815,
200-240
2805-2815, 380-480 V.

Pre-fuses

For all unit types, external pre-fuses must be fitted in
the mains supply to the frequency converter. For UL/
cUL applications with a mains voltage of 200-240 Volt,
use pre-fuses type Bussmann KTN-R (200-240 Volt)
or Ferraz Shawmut type ATMR (max. 30A). For UL/
cUL applications with a mains voltage of 380-480 Volt,
use pre-fuses type Bussmann KTS-R (380-480 Volt).
Prefuses for UL application /cUL
Bussmann
SIBA
Little Fuse
E4273
E180276
E81895
CC/JDDZ
RK1/JDDZ
RK1/JDDZ
LP-CC-20
5017906-02
KLS-R20
0
5017906-02
KLS-R25
5
5014006-05
KLS-R50
0
SIBA
Little Fuse
E180276
E81895
RK1/JDDZ
RK1/JDDZ
5017906-02
KLS-R20
0
5017906-02
KLS-R25
5
verter, which can be seen from the name-
plate.
400-Volt units with RFI-filters may not be
connected to mains supplies in which the
voltage between phase and earth is more
than 300 Volts. Please note that for the IT
mains and the delta earth the mains volt-
age can exceed 300 Volts between phase
and earth. Units with type code R5 can be
connected to mains supplies with up to
400 V between phase and earth.
See Technical data for correct dimensioning of cable
cross-section. See also the section entitled Galvanic
isolation for further details.
V,
and
VLT
Ferraz-
Ferraz-
Shawmut
Shawmut
E163267/
E163267/
E2137
E2137
CC/JDDZ
RK1/JDDZ
ATM-R25
A6K-20R
ATM-R20
A6K-25R
-
A6K-50R
Ferraz-
Ferraz-
Shawmut
Shawmut
E163267/
E163267/
E2137
E2137
CC/JDDZ
RK1/JDDZ
ATM-R25
A6K-20R
ATM-R20
A6K-25R