Shifting from Local operation to Remote operation in
parameter 002 Local/remote operation, while this pa-
rameter has been set to Remote operation: The local
reference will be replaced by the remote-operated ref-
erence signal.
014
Local stop
(LOCAL STOP)
Value:
Not active (DISABLE)
Active (ENABLE)
Function:
In this parameter, the local [STOP]-key can be engag-
ed or disengaged on the control panel and on the LCP
control panel.
Description of choice:
If Not active [0] is selected in this parameter, the
[STOP]-key will be inactive.
NB!
If Not active [0] is selected, the motor can-
not be stopped by means of the [STOP]-
key.
015
Local jog
(LOCAL JOGGING)
Value:
Not active (DISABLE)
Active (ENABLE)
Function:
In this parameter, the jog function on the LCP control
panel can be engaged/disengaged.
Description of choice:
If Not active [0] is selected in this parameter, the [JOG]-
key will be inactive.
= factory setting, () = display text, [] = value for use in communication via serial communication port
®
MG.27.A2.02 - VLT
is a registered Danfoss trademark
®
VLT
2800 Series
016
Local reversing
(LOCAL REVERSING)
Value:
Not active (DISABLE)
Active (ENABLE)
Function:
In this parameter you can select/deselect the reversing
function on the LCP control panel. The key can only
be used if parameter 002 Local/remote operation is set
[0]
to Local operation [1] and parameter 013 Localcon-
[1]
trol to Local control, open loop [1] or Local control as
parameter 100 [3].
Description of choice:
If Disable [0] is selected in this parameter, the [FWD/
REV] key will be disabled. See also parameter 200
Output frequency range.
017
Local reset of trip
(LOCAL RESET)
Value:
Not active (DISABLE)
Active (ENABLE)
Function:
In this parameter, the reset function on the control
panel can be engaged/disengaged.
Description of choice:
[0]
If Not active [0] is selected in this parameter, the reset
[1]
function will be inactive.
NB!
Select Not active [0], only if an external
reset signal has been connected via the
digital inputs.
[0]
[1]
[0]
[1]