Danfoss VLT 2800 Series Operating Instructions Manual page 41

Hide thumbs Also See for VLT 2800 Series:
Table of Contents

Advertisement

319
Analogue output terminal 42
(AO 42 FUNCTION)
Value:
No function (NO OPERATION)
External reference min.-max. 0-20 mA
(ref min-max = 0-20 mA)
External reference min.-max. 4-20 mA
(ref min-max = 4-20 mA)
Feedback min.-max. 0-20 mA
(fb min-max = 0-20 mA)
Feedback min.-max. 4-20 mA
(fb min-max = 4-20 mA)
Output frequency 0-max 0-20 mA
(0-fmax = 0-20 mA)
Output frequency 0-max 4-20 mA
(0-fmax = 4-20 mA)
Output current 0-I
0-20 mA
INV
(0-iinv = 0-20 mA)
Output current 0-I
4-20 mA
IINV
(0-iinv = 4-20 mA)
Output power 0-P
0-20 mA
M,N
(0-Pnom = 0-20 mA)
Output power 0-P
4-20 mA
M,N
(0-Pnom = 4-20 mA)
Inverter temperature 20-100 °C 0-20 mA
(TEMP 20-100 C=0-20 mA)
Inverter temperature 20-100 °C 4-20 mA
(TEMP 20-100 C=4-20 mA)
Function:
The analogue output can be used for stating a process
value. It is possible to choose two types of output sig-
nals 0 - 20 mA or 4 - 20 mA.
If used as a voltage output (0 - 10 V), a pull-down re-
sistor of 500 Ω must be fitted to common (terminal 55).
If the output is used as a current output the resulting
resistance from the equipment connected may not ex-
ceed 500 Ω.
Description of choice:
No function. Is selected if the analogue output is not to
be used.
External Ref
- Ref
0-20 mA/4-20 mA.
MIN
MAX
An output signal is obtained, which is proportional to
the resulting reference value in the interval Minimum
reference, Ref
- Maximum reference, Ref
MIN
rameters 204/205).
FB
-FB
0-20 mA/ 4-20 mA.
MIN
MAX
= factory setting, () = display text, [] = value for use in communication via serial communication port
40
An output signal is obtained, which is proportional to
the feedback value in the interval Minimum feedback,
FB
- Maximum feedback, FB
MIN
414/415).
[0]
0-f
0-20 mA/4-20 mA.
MAX
An output signal is obtained, which is proportional to
[1]
the output frequency in the interval 0 - f
202 Output frequency, high limit, f
[2]
0 - I
0-20 mA/4-20 mA.
INV
An output signal is obtained, which is proportional to
[3]
the output current in the interval 0 - I
0 - P
0-20 mA/4-20 mA.
M,N
[4]
An output signal is obtained, which is proportional to
the present output power. 20 mA corresponds to the
[5]
value set in parameter 102 Motor power, P
0 - Temp.
MAX
[6]
An output signal is obtained, which is proportional to
the present heatsink temperature. 0/4 mA corre-
[7]
sponds to a heatsink temperature of less than 20 °C,
and 20 mA corresponds to 100 °C.
[8]
[9]
323
[10]
Value:
No function (no operation)
[11]
Unit ready (unit ready)
Enable/no warning (enable/no warning)
[12]
Running (RUNNING)
Running in reference, no warning
(run on ref/no warn)
Running, no warnings
(RUNNING/NO WARNING)
Running in reference range, no warnings
(RUN IN RANGE/ NO WARN)
Ready - mains voltage within range
(RDY NO OVER/UNDERVOL)
Alarm or warning
(ALARM OR WARNING)
Current higher than current limit, par. 221
(Current limit)
Alarm (ALARM)
Output frequency higher than f
(above frequency low)
Output frequency lower than f
(pa-
MAX
(below frequency high)
Output current higher than I
(above current low)
MG.27.A2.02 - VLT
®
VLT
2800 Series
(parameter
MAX
MAX
0-20 mA/4-20 mA.
Relay output 1-3
(RELAY 1-3 FUNCT.)
LOW
HIGH
par. 223
LOW
®
is a registered Danfoss trademark
(parameter
MAX
).
INV
.
M,N
[0]
[1]
[2]
[3]
[4]
[5]
[6]
[7]
[8]
[9]
[10]
par. 225
[11]
par. 226
[12]
[13]