Function (Fct.)
C.1.19.1
Length unit
C.1.19.2
Conversion unit
C.1.20.0
Product density
C.1.21.0
Volume/Mass table
C.1.22.0
Linearisation table
C.2.0.0
I/O
C.3.0.0
Output 1(HART)
C.3.1.0
Output function
C.3.2.0
4 mA setting
C.3.3.0
20 mA setting
C.3.4.0
Output Range
C.3.5.0
Error handling
Input Range
m, cm, mm, inch, ft,
ft+inch+1/18inch,
ft+inch+1/32inch or free
unit. m
m³, L, US gal, GB gal, ft³,
bbl, Tons, kg, US tons, GB
tons or free unit. m³
0 to 999.99 kg/m³. 0
Level: 0 m or 0 ft to tank
height (C.1.2.0)+tank
bottom offset
(C.1.11.0)+reference
offset (C.1.10.0); volume:
0 m³ to tank volume.;
mass: 0 kg to mass of full
tank.
0 m or 0 ft to tank height
(C.1.2.0)+tank bottom
offset
(C.1.11.0)+reference
offset (C.1.10.0).
Level, distance, level
volume/mass, reflection,
distance
volume/mass.Level
-50m/0m³/0kg to 20 mA
setting (item C.3.3.0) of
output parameter (item
C.3.1.0) selected. 0
m/m³/kg
4 mA setting (item
C.3.2.0) of output
parameter (item C.3.1.0)
selected to value
dependant on output
function**. **
3.8-20.5 mA-NAMUR or 4-
20 mA. 3.8-20.5 mA-
NAMUR
3.6 mA, 22 mA or Hold. 22
mA
OPTIWAVE 7300 C
Handbook OPTIWAVE 7300 C
Description
Pick the length unit to be used in
volume/mass conversion table from the
list. If free unit is selected, the unit given in
item C.5.1.7 is used.
Pick the conversion unit to be used in the
conversion table from the list. If a mass
conversion unit is directly selected here, a
mass conversion table will be created
(volume conversion will then not be
possible). If free unit is selected, the unit
given in item C.5.1.9 is used.
A volume conversion table together with a
product density greater than 0, could be
used to calculate mass. If a mass
conversion unit has already been directly
selected, this menu is disabled.
Give number of value pairs needed. Enter
the length and corresponding volume/
mass values. 50 pairs maximum.
Can increase accuracy via on-site
calibration. Give the number of value pairs
needed. Use an accurate alternative
method of measurement to give a
corrective value to a given measurement.
50 pairs maximum.
Defines characteristics of output 1.
Pick the output function from the list. This
is independent of the measurement
function being displayed.
Assigns a measurement value to 4 mA
Assigns a measurement value to 20 mA
Defines the behaviour of the output 1 in
case an error occurs. Sets the effective
range of current output with or without
over-run.
Defines the behaviour of the current
output in case an error occurs.