Setting Levels Diagram - Omron E5CC-800 Specification & Installation Instructions

Digital temperature controller (simple type), 22.5 mm wide, and din track-mounting type,
Hide thumbs Also See for E5CC-800:
Table of Contents

Advertisement

E5@C-800
Operation

Setting Levels Diagram

This diagram shows all of the setting levels. To move to the advanced function setting level and calibration level, you must enter passwords. Some
parameters are not displayed depending on the protect level setting and the conditions of use.
Control stops when you move from the operation level to the initial setting level.
Only when Manual Mode was
used just before power OFF
Manual Control
Level
Used to set the
MV manually.
*1. Set the PF Setting parameter to a-m (Auto/Manual).
*2. The No. 1 display will flash when the keys are pressed for 1 s or longer.
54
Power ON
O
Press the
Key for at
S
Level changes
least 1 s or the
Key
automatically.
for at least 1 s. *1
Operation Level
Used for SP, alarm values,
and other basic settings
and monitoring.
O
Key for at
least 3 s while
a-m is
displayed.*2
S
Key for at least 1 s.*1
O
Press the
Key
for at least 3 s.*2
Initial Setting Level
Used to set the input type
and other basic settings.
Release protection and then
enter the password (−169)
for the amoV (Move to Advanced
Setting Level) parameter.
Advanced Function
Setting Level
Protect Level
O
M
Press the
and
Keys for at least 1 s.
Used to set protection
for operations.
O
Adjustment Level
Press the
Key once.
Used to change adjustment
parameters (PID constants,
adjustment sensitivity, etc.).
O
Press the
Key
for at least 1 s.
Control and auxiliary outputs stop.
O
Press
Key once
(models with
communications only).
Communications
Setting Level
Used to set communications.
O
Press the
Key for at least 1 s.
O
M
Press the
and
Keys
for at least 3 s.*2