E5CC-800/E5CC-B-800/E5CC-U-800
Characteristics
Indication accuracy
(at the ambient temperature of 23°C)
Simple transfer output accuracy
Influence of temperature *3
Influence of voltage *3
Influence of EMS. (at EN 61326-1)
Input sampling period
Hysteresis
Proportional band (P)
Integral time (I)
Derivative time (D)
Proportional band (P) for cooling
Integral time (I) for cooling
Derivative time (D) for cooling
Control period
Manual reset value
Alarm setting range
Affect of signal source resistance
Insulation resistance
Dielectric strength
Malfunction
Vibration
Resistance
Malfunction
Shock
Resistance
Weight
Degree of protection
Memory protection
Approved standards
Standards
Conformed standards
EMC
*1 The indication accuracy of K thermocouples in the -200 to 1300°C range, T and N thermocouples at a temperature of -100°C max., and U and
L thermocouples at any temperatures is ±2°C ±1 digit max. The indication accuracy of the B thermocouple at a temperature of 400°C max. is
not specified. The indication accuracy of B thermocouples at a temperature of 400 to 800° is ±3°C max. The indication accuracy of the R and
S thermocouples at a temperature of 200°C max. is ±3°C ±1 digit max. The indication accuracy of C/W thermocouples is (±0.3% of PV or ±3°C,
whichever is greater) ±1 digit max. The indication accuracy of PL II thermocouples is ±0.3% of PV or ±2°C, whichever is greater, ±1 digit max.
*2 However, the precision between 0 and 4 mA for a 0 to 20 mA output is ±1% FS max.
*3 Ambient temperature: -10°C to 23°C to 55°C, Voltage range: -15% to 10% of rated voltage
*4 K thermocouple at -100°C max.: ±10°C max.
*5 The unit is determined by the setting of the Integral/Derivative Time Unit parameter.
*6 The E5CC-U plug-in model is certified for UL listing only when used together with the OMRON P2CF-11 or P2CF-11-E Socket. The P3GA-11
is not certified for UL listing.
*7 Access the following website for information on certified models. http://www.ia.omron.com/support/models/index.html
*8 Refer to information on maritime standards in Shipping Standards on page 61 for compliance with Lloyd's Standards.
*9 Industrial electromagnetic environment (EN/IEC 61326-1 Table 2)
8
E5CC-800/E5CC-B-800
(±0.3% of indication value or ±1°C, whichever is greater) ±1 digit max. *1
Thermocouple:
Platinum resistance thermometer: (±0.2% of indication value or ±0.8°C, whichever is greater) ±1 digit max.
±0.2% FS ±1 digit max.
Analog input:
±5% FS ±1 digit max.
CT input:
E5CC-U-800
(±1% of indication value or ±2°C, whichever is greater) ±1 digit max. *1
Thermocouple:
Platinum resistance thermometer: (±0.2% of indication value or ±0.8°C, whichever is greater) ±1 digit max.
±0.2% FS ±1 digit max.
Analog input:
±0.3% FS max.*2
Thermocouple input (R, S, B, C/W, PL II): (±1% of indication value or ±10°C, whichever is greater) ±1 digit max.
Other thermocouple input: (±1% of indication value or ±4°C, whichever is greater) ±1 digit max. *4
Platinum resistance thermometer: (±1% of indication value or ±2°C, whichever is greater) ±1 digit max.
Analog input: ±1%FS ±1 digit max.
CT input: ±5% FS ±1 digit max.
50 ms
Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F)
Analog input: 0.01% to 99.99% FS (in units of 0.01% FS)
Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F)
Analog input: 0.1% to 999.9% FS (in units of 0.1% FS)
0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *5
0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *5
Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F)
Analog input: 0.1% to 999.9% FS (in units of 0.1% FS)
0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *5
0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *5
0.1, 0.2, 0.5, 1 to 99 s (in units of 1 s)
0.0 to 100.0% (in units of 0.1%)
-1999 to 9999 (decimal point position depends on input type)
Thermocouple: 0.1°C/Ω max. (100 Ωmax.)
Platinum resistance thermometer: 0.1°C/Ω max. (10 Ω max.)
20 MΩ min. (at 500 VDC)
3,000 VAC, 50/60 Hz for 1 min between terminals of different charge
2
10 to 55 Hz, 20 m/s
for 10 min each in X, Y, and Z directions
2
10 to 55 Hz, 20 m/s
for 2 hrs each in X, Y, and Z directions
2
100 m/s
, 3 times each in X, Y, and Z directions
2
300 m/s
, 3 times each in X, Y, and Z directions
E5CC-800/E5CC-B-800: Controller: Approx. 120 g, Adapter: Approx. 10 g
E5CC-U-800: Controller: Approx. 100 g, Adapter: Approx. 10 g
E5CC-800/E5CC-B-800: Front panel: IP66, Rear case: IP20, Terminals: IP00
E5CC-U-800: Front panel: IP50, Rear case: IP20, Terminals: IP00
Non-volatile memory (number of writes: 1,000,000 times)
cULus: UL 61010-1/CSA C22.2 No.61010-1 *6,
Korean wireless regulations (Radio law: KC Mark) (Some models only.) *7, Lloyd's standards *8
EN 61010-1 (IEC 61010-1)
EMI:
Radiated Interference Electromagnetic Field Strength: EN 55011 Group 1, class A
Noise Terminal Voltage:
EMS:
ESD Immunity:
Electromagnetic Field Immunity:
Burst Noise Immunity:
Conducted Disturbance Immunity:
Surge Immunity:
Voltage Dip/Interrupting Immunity:
EN 61326-1 *9
EN 55011 Group 1, class A
EN 61326-1 *9
EN 61000-4-2
EN 61000-4-3
EN 61000-4-4
EN 61000-4-6
EN 61000-4-5
EN 61000-4-11