Omron E5CC-800 Specification & Installation Instructions page 46

Digital temperature controller (simple type), 22.5 mm wide, and din track-mounting type,
Hide thumbs Also See for E5CC-800:
Table of Contents

Advertisement

E5DC-800
Characteristics
Indication accuracy
(when mounted individually, ambi-
ent temperature of 23°C)
Simple transfer output accuracy
Influence of temperature *3
Influence of voltage *3
Influence of EMS. (at EN 61326-1)
Installation influence
(E5DC-800 only)
Input sampling period
Hysteresis
Proportional band (P)
Integral time (I)
Derivative time (D)
Proportional band (P) for cooling
Integral time (I) for cooling
Derivative time (D) for cooling
Control period
Manual reset value
Alarm setting range
Influence of signal source resis-
tance
Insulation resistance
Dielectric strength
Malfunction
Vibration
Resistance
Malfunction
Shock
Resistance
Weight
Degree of protection
Memory protection
Approved standards
Standards
Conformed standards EN 61010-1 (IEC 61010-1)
EMC
*1 The indication accuracy of K thermocouples in the −200 to 1,300°C range, T and N thermocouples at a temperature of −100°C or less, and U
and L thermocouples at any temperature is ±2°C ±1 digit max. The indication accuracy of B thermocouples at a temperature of 400°C max. is
not specified. The indication accuracy of B thermocouples at a temperature of 400 to 800°C is ±3°C max.
The indication accuracy of R and S thermocouples at a temperature of 200°C max. is ±3°C ±1 digit max. The indication accuracy of C/W
thermocouples is (±0.3% of PV or ±3°C, whichever is greater) ±1 digit max.
The indication accuracy of PLII thermocouples is (±0.3% of PV or ±2°C, whichever is greater) ±1 digit max.
*2 However, the precision between 0 and 4 mA for a 0 to 20 mA output is ±1% FS max.
*3 Ambient temperature: −10 to 23 to 55°C, Voltage range: −15% to 10% of rated voltage
*4 K thermocouple at −100°C max: ±10°C max.
*5 The unit is determined by the setting of the Integral/Derivative Time Unit parameter.
*6 Refer to your OMRON website for the most recent information on applicable models.
*7 Refer to information on maritime standards in Shipping Standards on page 61 for compliance with Lloyd's Standards.
*8 Industrial electromagnetic environment (EN/IEC 61326-1 Table 2)
46
(±0.3% of indication value or ±1°C, whichever is greater) ±1 digit max. *1
Thermocouple:
Platinum resistance thermometer: (±0.2% of indication value or ±0.8°C, whichever is greater) ±1 digit max.
±0.2% FS ±1 digit max.
Analog input:
±5% FS ±1 digit max.
CT input:
±0.3% FS max.*2
Thermocouple input (R, S, B, C/W, PL II): (±1% of indication value or ±10°C, whichever is greater) ±1 digit max.
Other thermocouple input: (±1% of indication value or ±4°C, whichever is greater) ±1 digit max. *4
Platinum resistance thermometer: (±1% of PV or ±2°C, whichever is greater) ±1 digit max.
Analog input: ±1% FS ±1 digit max.
CT input: ±5% FS ±1 digit max.
R, S, B, W, or PLII thermocouple: (±1% of PV or ±10°C, whichever is greater) ±1 digit max.
Other thermocouple: (±1% of PV or ±4°C, whichever is greater) ±1 digit max. *4
50 ms
Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F)
Analog input: 0.01% to 99.99% FS (in units of 0.01% FS)
Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F)
Analog input: 0.1% to 999.9% FS (in units of 0.1% FS)
0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *5
0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *5
Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F)
Analog input: 0.1% to 999.9% FS (in units of 0.1% FS)
0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *5
0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *5
0.1, 0.2, 0.5, 1 to 99 s (in units of 1 s)
0.0% to 100.0% (in units of 0.1%)
−1,999 to 9,999 (decimal point position depends on input type)
Thermocouple: 0.1°C/Ω max. (100 Ω max.), Platinum resistance thermometer: 0.1°C/Ω max. (10 Ω max.)
20 MΩ min. (at 500 VDC)
3,000 VAC, 50/60 Hz for 1 min between terminals of different charge
2
10 to 55 Hz, 20 m/s
for 10 min each in X, Y and Z directions
2
10 to 55 Hz, 20 m/s
for 2 hr each in X, Y, and Z directions
2
100 m/s
, 3 times each in X, Y, and Z directions
2
300 m/s
, 3 times each in X, Y, and Z directions
Main unit: Approx. 80 g, Terminal unit: Appox. 40 g
Main unit: IP20, Terminal unit: IP00
Non-volatile memory (number of writes: 1,000,000 times)
cULus: UL 61010-1/CSA C22.2 No.61010-1, Korean wireless regulations (Radio law: KC Mark) (Some
models only.) *6, Lloyd's standards *7
EMI:
Radiated Interference Electromagnetic Field Strength: EN55011 Group 1, class A
Noise Terminal Voltage:
EMS:
ESD Immunity:
Electromagnetic Field Immunity:
Burst Noise Immunity:
Conduction Disturbance Immunity:
Surge Immunity:
Voltage Dip/Interrupting Immunity:
EN61326-1 *8
EN55011 Group 1, class A
EN61326-1 *8
EN61000-4-2
EN61000-4-3
EN61000-4-4
EN61000-4-6
EN61000-4-5
EN61000-4-11