7- segment
Alarm
Check points
monitor
descripation
display
Momentary overload
Excessive deceleration rate with
oCPd
?
2
during deceleration
GD
setting for current limiting
function (F1701) too high?
Overload during
Motor operated with an excessive
oLA
acceleration
load?
Overload during
oLn
constant speed
Electrothermal level set properly?
Overload during
oLd
deceleration
Load GD
Overvoltage during
ouA
Whether start-up occur during
acceleration
idle run.
Overvoltage during
oun
Whether motor is turned by
constant speed
Other force?
Overvoltage during
oud
Excessive deceleration
deceleration
Brake resistor
ouP
Whether the frequency of
overvoltage
braking is too high?
protection
Feedback signal cable
Disconnection of
GAL1
disconnected?
feedback signal cable
Feedback signal correct?
(during PID control
Gain frequency correct?
action)
(F1402、F1404)
Actions
Extend the deceleration time.
Decrease the setting value.
Reduce the load.
Increase the capacity of Inverter and
Motor.
2
too larger?
Change to flying start mode.
Redesign the system so that the motor is not
driven by external force.
Use a brake resistor with a larger capacity.
Extened the deceleration time.
2
(so that GD
of the load is met)
Reduce the braking frequency.
Increase the brake resistor capacity.
Checking feedback signal cable and connected
securely.
Set gain frequency properly.
(F1402、F1404)
-71-