Code
Function Name
PID1 operation polarity
3011
switching
3012
PID1 gain polarity switching
3013
PID1 command value
gain
3014
PID1 feedback value
gain
3015
PID1 control proportional
gain( negative F3012=2)
3016
PID1 control integral time
(negative :F3012=2)
3017
PID1 control command value
3018
PID1 control feedback value
(communication function
3019
Frequency corresponding to
PID1 control max. command
value
3101
PID2 command value
Input switching
Data Content
1:Command value-feedbakck value
2:Feedback value-command value
1: The positive or negative deviation indicates the
same gain
2: The positiveor negative deviation indicates the
different gain
0~50
0~50
0~100
0.01~100 sec.
0~6000
0~6000
0~600Hz
1: Frequency
2: External analog VRF voltage(0~5V)
3: External analog VRF voltage(0~10V
or potentiometer)
4: External analog V/I voltage(0~5V)
5: External analog V/I voltage(0~10V
or potentiometer)
9: External analog V/I current(4~20mA)
11: Function code setting(F3117)
-52-
Setting
Factory
resolution
preset
1
1
1
1
0.01
1
0.01
1
0.01
0.1
0.01 sec.
0.1
0.1
0
0.1
0
0.01Hz
60
1
0