F3406 is valid code under the control mode of pressure command given
While F3002=1、3、5 : Set pressure value at 5V
While F3002=2、4、6 : Set pressure value at 10V
While F3002=7、8、9 : Set pressure value at 20mA
F3407
Analog feedback lower pressure limit
F3407 is valid code under pressure command given control mode.
While F3002=1~6 : Pressure value setting as at 0V
While F3002=7~9 : Pressure value setting as at 4mA
F3408
Upper pressure value limit PH
F3408 is valid code under the control mode of pressure command given.
While F3001=2、4 : Pressure value setting as at 5V
While F3001=3、5 : Pressure value setting as at 10V
While F3001=9 :
Pressure value setting as at 20mA
While F3405>F3408 , Pressure value is limited to the upper limit setting value of F3408
F3409
Lower pressure value limit PL
F3409 is valid code under the control mode of pressure command given.
While F3001=2、3、4、5 : Set pressure value at 0V
While F3001=9 : Set pressure value at 4mA
While F3405<F3409 , Pressure command is limited to the lower setting value of F3409 limit
F3410
The slop of pressure acceleration/deceleration
F3407 is the ratio of setting pressure variations under the control mode of pressure command given
Higher setting value, the faster change of speed.
F3411
Allowable devitation for Motor switching
This code for setting the allowable devitation for Motor switching, 1% of pressure value for setting
unit. The suitable value in setting will be improved the stabilities of system, and in avoid of
frequently switching action.