Water Supply Function F34Xx - Sanken SAMCO-NS Series Instruction Manual

Compact vector control inverter, simple version, vvvf inverter
Table of Contents

Advertisement

Water Supply Function F34xx

Water Supply Function F34xx
Code
Function Name
Data Content
Water supply mode
3401
0:Water supply function disabled
Selection
1:Single Pump Mode
Lower limit range
3402
0.1~10 Min.
continued time T1
Sleep wake up ratio
3403
30~95%
K
Sleep wake up
3404
0.1~10 min.
Judgement time Tp
Pressure command
3405
0~9.999MPa
Pref
Analog feedback upper
3406
0~±9.999MPa
pressure limit
Analog feedback lower
3407
0~±9.999MPa
Pressure limit
Upper pressure value
3408
0.001~9.999MPa
limit Ph
Lower pressure value
3409
0~9.999MPa
limit PL
The slip of pressure in
3410
0.001~9.999MPa
Acceleration
/Deceleration
Allowed deviation on
3411
0.0-20.0%
Motor switching
Setting
resolution
1
0.1min.
1%
0.1min.
0.001MPa
0.001MPa
0.001MPa
0.001MPa
0.001MPa
0.001MPa
0.1%
-57-
Factory
preset
0
5
50
5
0
0
0
1
0
0.1
0.0

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents