Code
Function Name
Data Content
Frequency corresponding
3119
0~600Hz
to PID2 control max.
command value
3123
1:Direct input mode
PID start mode seleciton
2:Condition input mode
1:Direct end mode
3124
PID end mode selection
2:Condition end mode
3125
PID end setting value
1~100%(upper frequency limit standard)
3127
0:Only warning
PID feedback signal
abnormal detection time
0.01~119.99 sec.
120:No abnormal detection
0:Open loop control
3201
PID control action selection
1:PID1 control
2:PID2 control
4:External terminal switching PID control
5:Timing switch PID control
0:No external PID control
3203
External PID control
1:PID1 external control
selection
2:PID2 external control
4:PID1 and PID2 external control
1:Operation interlock with Inverter operation
3204
External PID operation
2:PID output after power input
mode selection
3:PID output controled by external terminals
0:without command value addition calculation
3205
PID constitution selection
1:with command value addition calculation
3206
Command value addition
0.01~100
Calculation PID control
gain
3207
PID1/PID2 switching time
0.1~6000 min.
3301
Reading PID1 command
Ready only
Value
3302
Reading PID1 feedback
Ready only
Value
Setting
resolution
0.01Hz
1
1
0.1%
0.01 sec.
1
1
1
1
0.01
0.1 min.
1
1
-55-
Factory
preset
60
1
1
20
2
0
0
1
0
1
0.1
---
---