Operation Manual
T&H-com-flt
Alarm
Possible
If the inverter is equipped with heating and dehumidification function and the
communication between the temperature & humidity board and the device is
reason
poor, this alarm occurs
Measure
Contact Sungrow
The operation LED is green.
Remark
10.5
Other Faults
Fault
Inverter shuts down shortly after start-up
Possible
DC input voltage just reaches the inverter start-up voltage. The voltage will
reason
decrease and inverter will stop when it is under load.
Measure
Design the serial and parallel connection in accordance with the open circuit
voltage; increase the input DC voltage; avoid adopting the critical voltage
Remark
-
Fault
LCD Display Cannot Start or Stop Inverter
Possible
Communication malfunction between the LCD display and the DSP; LCD power
reason
supply malfunction
Measure
Check the connection between the LCD display and the DSP when inverter is
voltage-free
Remark
-
Fault
Communication Failure with PC
Possible
Possible reasons are various. Please refer to the Measure for troubleshooting
reason
Check if the address and the Baud rate of the LCD are the same with that of
Measure
PC
Check to ensure the circuits are properly connected and if the RS485
communication is adopted, the A and B ports are connected correctly
Check if the communication converters are matched. Communicate again
after replacing the converter
The monitor disk is installed incorrectly. It is recommended to reinstall the
disk
If all the above-mentioned items are correct and this fault continues, please
replace the PC communication module on the LCD display
Remark
The monitor disk might be incompatible with the antivirus software and thus
cannot be installed correctly. You are recommended to disable the antivirus
software and then install the monitor software.
If the fault still occurs, please contact Sungrow
10. Troubleshooting
61