10 Troubleshooting
Fault
LVRT Run
Grid voltage is below 0.9Un and the LVRT function is enabled
Possible
reason
Warn will disappear automatically when grid voltage recover normal
Measure
Remark
-
CT-Unbalanced
Fault
Possible
Current transformer (CT) on the inverter control cabinet is abnormal
reason
Measure
Check and service the CT on the measuring board when inverter is voltage-free
-
Remark
Fault
RISO-low
Inverter DC side insulation resistance is lower than the set value.
Possible
reason
Measure
-
Remark
Only alarm display. Inverter can operate normally.
DC Sensor-err
Fault
Possible
Inverter DC sensor abnormal
reason
Check and service the DC sensor when inverter is voltage-free
Measure
-
Remark
10.5
Other Faults
Inverter Shuts Down Shortly After Start-Up
Possible reason: DC input voltage just reaches the inverter start-up voltage. Voltage will decrease
and inverter will stop when it is under load.
Solution: design the serial and parallel connection in accordance with the open circuit voltage;
increase the input DC voltage; avoid adopting the critical voltage.
Hear-Sink is Over-Temperature
Possible reason: cooling fan failure; over-temperature of the air inlet; bad ventilation of the
switch room, etc..
Solution: check and replace the cooling fan; reduce the temperature of the switch room; clean
the air duct and widen the air duct.
Noise is Too Loud during Inverter Operation
Possible reason: abnormal operation of the inverter and transformer; fan failure.
Solution: check if the power is within the permissible range; measure if the grid-connected
current and voltage waveform are normal (if not, the noise will be loud and the transformer will
be overheating); check and replace the fan.
LCD Display Cannot Start or Stop Inverter
Possible reason: communication malfunction between the LCD display and the DSP; LCD power
supply malfunction.
Solution: check the connection between the LCD display and the DSP.
50