Code
Cause
Text message
•
F264
Installation/Setup
•
error
•
F265
Measurement func-
•
tion disturbed
Tab. 5: Error codes and text messages, information on causes as well as corrective measures
Function check
Code
Cause
Text message
•
C700
Simulation active
Tab. 6: Error codes and text messages, information on causes as well as corrective measures
Out of specification
Code
Cause
Text message
•
S600
Impermissible elec-
tronics temperature
•
S601
Overfilling
Tab. 7: Error codes and text messages, information on causes as well as corrective measures
Maintenance
Code
Cause
Text message
•
M500
Error during the re-
set "delivery status"
•
M501
Error in the non-
active linearisation
table
•
M502
Error in the diag-
nostics memory
VEGAPULS 62 • Profibus PA
Adjustment not within the vessel
height/measuring range
Max. measuring range of the
instrument not sufficient
Sensor no longer carries out a
measurement
Operating voltage too low
A simulation is active
Temperature of the electronics
in the non-specified range
Danger of vessel overfilling
The data could not be restored
during the reset to delivery
status
Hardware error EEPROM
Hardware error EEPROM
9 Diagnosis, asset management and service
Rectification
•
Check or correct installation
and/or parameter settings
•
Use an instrument with bigger
measuring range
•
Check operating voltage
•
Carry out a reset
•
Disconnect operating voltage
briefly
Rectification
•
Finish simulation
•
Wait for the automatic end after
60 mins.
Rectification
•
Check ambient temperature
•
Insulate electronics
•
Use instrument with higher
temperature range
•
Make sure that there is no
further filling
•
Check level in the vessel
Rectification
•
Repeat reset
•
Load XML file with sensor data
into the sensor
•
Exchanging the electronics
•
Send instrument for repair
•
Exchanging the electronics
•
Send instrument for repair
DevSpec
Diagnosis Bits
Bit 10
Bit 11
DevSpec
Diagnosis Bits
Bit 19
DevSpec
Diagnosis Bits
Bit 18
Bit 20
DevSpec
Diagnosis Bits
Bit 13
Bit 14
Bit 15
69