Installing The Eip-200S Ethernet/Ip Adapter - Siemens SIMATIC S7 EIP-200S System Manual

Ethernet/ip adapter distributed i/o system
Table of Contents

Advertisement

Installation and wiring

3.3 Installing the EIP-200S Ethernet/IP Adapter

3.3
Installing the EIP-200S Ethernet/IP Adapter
Features
● The EIP-200S Ethernet/IP Adapter connects the ET 200S with the network.
● The EIP-200S Ethernet/IP Adapter transfers data between the higher-level controller and
the I/O modules.
Prerequisites
The prerequisites for installation are shown below
● The rail must be installed.
● All the terminal modules must be installed to the right of the interface module. The
maximum configuration of the ET 200S distributed I/O system is 63 modules (including
power modules, I/O modules, motor starters, and terminating module).
Tools required
3 mm screwdriver
Installing the EIP-200S Ethernet/IP Adapter
To install the EIP-200S Ethernet/IP Adapter, follow the steps below:
1. Hang the interface module on the rail.
2. Tip the interface module back until you hear the locking mechanism engage.
Removing the EIP-200S Ethernet/IP Adapter
The interface module is wired, and the terminal modules are on the right:
1. Switch off the supply voltage on the interface module.
2. Disconnect the wiring connector and the bus connector on the interface module.
3. Use a screwdriver to push the locking mechanism on the interface module down until the
mechanism stops, and move the interface module to the left.
– Note: The locking mechanism is under the interface module.
4. With the locking mechanism depressed, tip the interface module forward so that it comes
off the rail.
54
EIP-200S Ethernet/IP Adapter Distributed I/O System
System Manual, 06/2018, A5E44345053-AB

Hide quick links: