Siemens SIMATIC S7 EIP-200S System Manual page 34

Ethernet/ip adapter distributed i/o system
Table of Contents

Advertisement

EIP-200S Ethernet/IP Adapter
2.6 Device profile: supported CIP objects
Attribute
ID
6
12
13
Table for "Interface status", Attribute 1
Bit(s):
0 - 3
4
5 - 31
Common services for TCP/IP Interface Object
Service
code
0x01
0x0E
0x10
34
Access
Description
rule
Set
Host name
Set
Ethernet/IP
QuickConnect
Set
Encapsulation
Inactivity
Timeout
Called:
Definition
Interface Con-
Indicates the status of
figuration Status
the Interface Configura-
tion attribute.
Mcast Pending
Indicates a pending configuration change in the TTL Value and/or
McastConfig attributes. This bit is set when either the TTL Value or
McastConfig attribute is set, and cleared the next time the device starts.
Reserved
Reserved for future use and set to zero.
Service available
Class
Instance
Yes
Yes
Yes
Yes
No
Yes
Data type Default value
STRING
0x00E (length =
14) plus hex
equivalent of
"br+MAC" (2+12
digits)
BOOL
0
UINT
0 = The Interface Configuration attribute has not
been configured
1 = The Interface Configuration attribute con-
tains valid configuration obtained from BOOTP,
DHCP, or non-volatile storage.
2 = The Interface Configuration attribute con-
tains valid configuration, obtained from hard-
ware settings (for example, pushwheel,
thumbwheel, etc.)
3 - 15 = Reserved for future use
Service name
Description
Get_Attribute_All
Supplies contents of all attributes
Get_Attribute_Single
Supplies contents of the appropriate
attribute
Set_Attribute_Single
Modifies an attribute value
EIP-200S Ethernet/IP Adapter Distributed I/O System
System Manual, 06/2018, A5E44345053-AB
Semantics of values
ASCII characters. Maxi-
mum length is 48 charac-
ters. Padded to an even
number of characters (pad
not included in length). A
length of 0 indicates no
host name is configured.
0 = disabled
1 = enabled
0 = disabled
1-3600 = timeout in sec-
onds
Default = 120