EIP-200S Ethernet/IP Adapter

Hardware configuration
See the separate manual "EIP ET200 Configuration Tool User Manual" for information on
the EIP ET200 Configuration Tool for the EIP-200S Ethernet/IP Adapter. The manual can be
found on the Companion Disk that shipped with the product, or downloaded from the
Siemens Service & Support Website (http://support.automation.siemens.com).
LED status indicators
The EIP-200S Ethernet/IP Adapter module has three bi-color LEDs that provide diagnostic
information about the current state of the device and provide an indication of any faults. The
LEDs conform to the behaviors defined in the ODVA Ethernet/IP Adaptation of CIP Adapter
Specification for the Module Status and Network Status LEDs, and in this manual for I/O
Status LEDs.
LED status indicator: Module Status LED
The bi-color Module Status LED indicates the current state of the EIP-200S Ethernet/IP
Adapter, as described in the following table:
State
Off
Flashing green
Green
Flashing red
Red
EIP-200S Ethernet/IP Adapter Distributed I/O System
System Manual, 06/2018, A5E44345053-AB
Description
No power applied to device.
Device has not been configured.
Invalid parameter data.
Device has initialized successfully and no errors
were detected.
Recoverable fault.
Device needs commissioning due to configuration
error:
Invalid parameter data
Invalid slot configuration data.
Unrecoverable fault detected: hardware failure.