Installation and wiring
3.9 Wiring the ET 200S
Connecting cable shields
We recommend you use the shield contact to connect cable shields (in the case of analog
electronic modules, the 1COUNT 24V/100kHz electronic module and the 1SSI electronic
module, for example).
To connect cable shields, perform the following steps:
1. Remove the insulation material from the area around the shield terminal, and clamp the
cable shield in the shield terminal (above the conductor rail). The shield terminal is
suitable for one cable with a max. ∅ of 8 mm or two cables with a max. ∅ of 4 mm each.
2. Tighten the shield terminal (approximately 0.5 Nm).
3. Repeat steps 1 and 2 if you want to connect additional cable shields.
4. Strip the insulation from the ground wire (from 6 mm to 25 mm
ground connection terminal (under the conductor rail). Tighten the ground connection
terminal
(2 Nm to 2.5 Nm).
5. Attach the other end to the ground bus.
74
), and insert it in the
2
EIP-200S Ethernet/IP Adapter Distributed I/O System
System Manual, 06/2018, A5E44345053-AB