Fluke CertiFiber Pro User Manual page 91

Optical loss test set
Hide thumbs Also See for CertiFiber Pro:
Table of Contents

Advertisement

3
Do an Autotest.
4
Halfway through the test, the tester tells you to switch the
input and output fibers.
Switch the connections at both ends of the patch
panel or fiber under test, not at the tester's and
remote's ports. If you disconnect a test reference
cord from an output port on the tester or remote,
the reference value will be unreliable.
The directions Main>Remote (main to remote)
and Remote>Main (remote to main) in the bi-
directional results are only the directions of the
optical signals for the second half of the test. If a
fiber fails, the direction does not tell you the
location of the problem.
5
If Auto Save is on and the tester is in Smart Remote mode, the
tester uses the next two IDs to save the results for the two
fibers.
If Auto Save is off, the SAVE RESULT screen shows the next two
IDs available. You can change the IDs if necessary.
Chapter 3: How to Certify Fiber Cabling
Caution
Note
Bi-Directional Tests
81