Note:
Allow 100lbs (45kg) per linear foot hanging weight.
Do not lift exhaust hoods from their end panels. Lift from four corners.
All exhaust hoods and control panels are fitted together and factory tested prior to shipping for
alignment and operation.
5.
Duct connections must meet NFPA 96 requirements and applicable local codes. Size of
connection is indicated on exhaust hood drawing. Connection is to be made after exhaust hood
is hung.
6. Electrical circuits should be connected according to the standard switch panel wiring diagram.
UV hoods have additional wiring requirements to connect the control panel to the hoods, as well
as connections between multiple hoods operated from the same control panel. The following
electrical service requirements are field installed:
A 120 volt, 15 amp uninterrupted supply to the control panel.
A 120 volt circuit from the control panel to the exhaust fan starter coil or relay.
A 120 volt circuit from the control panel to the make up air fan starter coil or relay.
A separate 120 volt, 15 amp supply to the light fixture junction box(es) on top of each hood.
Note: The selector switch on the control panel controls the exhaust fan operation.
Please see job specific wiring connection information in the job submittal drawings and an
additional wiring diagram is included in the electrical control box shipped with the job. Additional
copies may be obtained from the factory if this wiring diagram is missing or lost. Please be
prepared to provide the job order number (found on the sales invoice), job name and address
or submittal drawing series number when contacting the factory for this or other job specific
documents.
7 .
Grease filters and grease cups must be installed in place before start-up.
8.
Halton hood come standard with high output, long lasting LED light fixtures. Optionally
incandescent or recessed fluorescent fixtures may be ordered. Please note only install 100 watt
maximum light bulbs in incandescent light fixtures. Fluorescent bulbs should be type T8, 36"
or 48" long in fluorescent fixtures. **Note: Halton does not provide bulbs for incandescent or
fluorescent lights.
9. If Closure Panels are supplied by Halton see pg. 9 for details on the installation.
10. For multiple hoods end to end, or back to back see pg. 8 for Installation of Splice Strips and
U-Channels.
11. Protect the hood from damage under normal job site conditions, until all work is complete and
system is ready to be put into operation.