UV CONTROL PANEL - SEqUENCE OF OPERATION
System ON
• UV On
• Exhaust fan On
• Makeup fan On
System OFF
• UV Off
• Exhaust fan runs for 30 sec to exhaust ozone from the system and turns Off
• Makeup fan On
Fire
• Exhaust fan will continue to run or it will start (even if system is off).
(Exhaust fan can be turned off in fire mode if required by local fire code).
• Make up fan will turn off or remain off.
• UV is turned off or remains off.
Main Screen
System ON/OFF
toggle switch
To turn the system ON, touch the ON/OFF toggle switch on a Main screen.
Exhaust and make up fan are turned on, UV is ON
Note:
System can be configured to be turned On/Off remotely with dry, open contacts connected to
terminals 1 and 4. In this case the On/Off push button on a touch screen will not be available.
Capture Ray
®
UV Operation & Maintenance Manual
Button to switch to
Alarm Screen
Button to switch
to UV hours of
operation
22
System ON/OFF
Status Display
UV Status Display