No.
9
Data logging registration was attempted to a failed memory.
10
In registration of the data logging, a nonexistent program name was specified.
A program name (which exists in the CPU module but is not registered to the
11
program setting in PLC Parameter) was specified in registration of the data
logging.
12
In registration of the data logging, a nonexistent device number was specified.
In registration of the data logging, a nonexistent step number or any other
13
than the head step number of an instruction was specified.
Registration of the trigger logging was attempted with the trigger condition(s)
14
already met.
When "Stop" is selected for the setting of operation in the case of exceeding
the maximum number of files to be saved, a data logging registration was
attempted in a state where existing saved files are the predetermined
15
maximum number of files or more. Or, when "Overwrite" is selected, a data
logging registration was attempted in a state where existing saved files are
more than the predetermined maximum number of files.
Writing or deleting data logging settings, or data logging operation was
16
attempted to a setting that has been already registered.
While the data logging function is in operation (the logging status is
"Executing", "Saving the logging data", "Completed", "Pausing", or "Error"),
17
registration of a data logging was attempted to the same destination as the
currently executing data logging.
During online change, registration of a data logging, in which "Step No." is
18
specified in "Sampling" or "Trigger", was attempted.
While the trigger logging function is in operation with a device specified in
Trigger (the logging status is "Executing", "Saving the logging data",
19
"Completed", "Pausing", or "Error"), registration of a trigger logging was
attempted with a device specified in Trigger.
Registration of a data logging was attempted during execution of the sampling
20
trace function.
Writing or deleting data logging settings, or data logging registration was
21
attempted during execution of auto logging.
During execution of auto logging, a data logging was not registered due to
22
registration failure of another setting No.
Registration of a data logging, in which an invalid device name was specified,
23
was attempted.
Registration of a data logging, in which an invalid device modification was
24
specified, was attempted.
Re-registration of the previously registered data logging setting was
25
attempted. However, the corresponding file does not exist.
Data logging registration was attempted to a memory where no common
26
setting exists.
Registration of a trigger logging was attempted even though the specified
27
number of records has exceeded the number of records that can be collected
for the specified data logging buffer capacity.
Data logging operation was performed during execution of the CPU module
28
change function with SD memory card (backup and restoration).
Registration of a data logging, in which a device of a nonexistent module or
29
an inaccessible device was specified, was attempted.
While the data logging function is in operation (the logging status is
30
"Executing", "Saving the logging data", "Completed", "Pausing", or "Error"),
execution of an inexecutable function was attempted.
When creating the data logging file, the target memory does not have the
31
required free space.
The SD memory card is write-protected. Or, data logging file writing to the
32
target memory was not completed due to incorrect folder or file configuration.
Error cause
CHAPTER 13 TROUBLESHOOTING
Value in special register
Timing of
(Data logging error cause
occurrence
information)
200
201
202
203
204
Registration
205
207
• Writing settings
• Deleting settings
• Registration
209
20A
Registration
20B
20C
• Writing settings
• Deleting settings
• Registration
20D
20E
20F
Registration
211
212
215
• Registration
• Cancel
217
Registration
During execution
501
502
Error response
No.
4021
H
H
4022
H
H
4083
H
H
4031
H
H
4088
H
H
4064
H
H
4277
H
H
4060
H
427B
H
H
410A
H
H
4272
H
H
4273
H
H
4275
H
H
4030
H
H
4032
H
H
41C5
H
H
427A
H
H
4274
H
H
4332
H
4043
H
H
4276
H
H
H
181