MODBUS
Communications
7.1.

Introduction

The MRLDS-250 gas detector can be configured to
communicate on an RS-485 network using 
MODBUS-RTU protocol. Before configuring the gas
detector for MODBUS communications, be sure your
network connection is complete and your network 
termination switches are set appropriately. Refer to
Section 3, Wiring and Configuration for details.
7.3.

Analog Input Registers

Analog input registers are read only and use 
function code 04.
Reg
Description
1000
Concentration gas level
1001
Concentration gas level
1002
Reserved
1003
Full scale detector level
1004
Alarm setpoint (% full
scale)
1005
Gas detector timer
1006
Node address
1007
Software version
1008
Reserved
1009
Reserved
1010
Reserved
1011
Reserved
1012
16-bit fault code
Table 7-1 - Analog Input Registers
24 • MRLDS-250 Infrared Gas Detector I&O Manual
7.2.
There are 255 selections available to be set
electronically, from addresses 1 to 255 inclusive. 
MODBUS data with a zero in the address field is 
received by all detectors (regardless of the address 
selected) to enable the master device to broadcast 
simultaneously to all the detectors.
Refer to the specifications section for information on
RS-485 network communications parameters such as
data bits, stop bits, and more.
Range
Units
0-100
%FS
0-65, 535
PPM
0-65, 535
PPM
0-100
%
0-65, 535
hours
1-247
none
none
0-65535
none
Communications
Settings
P.-##
--
--
--
--
--
--
P.-10
--
--
--
--
--
--
026-1315 Rev 4