Analog Output Registers - Emerson MRLDS-250 Installation And Operation Manual

Infrared gas detector
Hide thumbs Also See for MRLDS-250:
Table of Contents

Advertisement

7.4.

Analog Output Registers

Analog output registers are readable (using function code 03) and writable (using function code 06).
Reg
Description
2000
Alarm setpoint
2001
Alarm ON delay
(Alarm flag register
3000 is set to 1)
2002
Buzzer mute time
2003
Alarm OFF delay
2004
Relay action
2005
Relay latching enable
2006
Buzzer enable
2007
Display mode
2008
Analog output type
2009
Baud rate
2010
Stop bits
2011
Gas curve number
2012
Analog output full scale
PPM (R/O)
2013
Parity
Table 7-2 - Analog Output Registers
Analog Output Registers
Range
Units
75-3500
PPM
0-15
min
0-59
min
0-15
min
0=NO
none
1=Failsafe
0=Disable
none
1=Enable
0=Disable
none
1=Enable
0=Off
none
1=On
0=0-5 V
none
1=1-4 V
2=0-10 V
3=2-10 V
4=4-20 ma
0=9600
none
1=19200
1 or 2
none
1 to 4
none
(broadband
unit) or gas
type (gas
specific)
100-3500
PPM
0=None
none
1=Odd
2=Even
P.-##
P.-02
P.-04
P.-12
P.-05
P.-06
P.-07
P.-08
P.-09
P.-03
P.-13
P.-14
P.-11
P.-16
P.-15
MODBUS Communications • 25