7.5.
Input Status Flags
Input Status Flags are readable (using function code 02).
Reg
3000
Alarm flag (0 or 1=Alarm)
3001
Relay state (0 or 1=energized)
3002
Detector fault (0 or 1=fault)
3003
Red LED state (0 or 1=ON)
3004
Green LED state (0 or 1=powered
on)
3005
Reserved
3006
Start up (0=normal operation,
1=warming up)
3007
Reserved
3008
Reserved
Table 7-3 - Input Status Flags
7.6.
Output Status Flags
Output Status Flags are readable (using function code 01) and writable (using function code 05).
Reg
4000
Buzzer flag (0 or 1=ON)
4001
Test required (If operating for >1
year). (1=requires testing)
Table 7-4 - Output Status Flags
26 • MRLDS-250 Infrared Gas Detector I&O Manual
Description
Description
Range
P.-##
0-1
- -
0-1
- -
0-1
- -
0-1
- -
0-1
- -
- -
0-1
- -
- -
- -
Range
P.-##
0=Off
- -
1=On
0=Okay
- -
1=Test
026-1315 Rev 4