Power Range 1000Va - 3000Va (230V Model) - Toshiba T1000 Series Installation And Operation Manual

Single-phase 1000-3000va
Hide thumbs Also See for T1000 Series:
Table of Contents

Advertisement

16.2

POWER RANGE 1000VA - 3000VA (230V MODEL)

GENERAL
Rated power
Capacity (W)
Topology
Phase
INPUT
Nominal Input Voltage
Input Voltage Range
Input Frequency
Input Power factor
Rated Input Current
OUTPUT
Output Power Factor
Nominal Output Voltage
Other Output Voltage:
Voltage regulation:
Voltage distortion
Rated Current @ 230 VAC
Output Frequency
Frequency regulation
Wave Form Type
Overload capacity
Bypass
Crest Factor
Efficiency
WARNING:
When power is supplied by external batteries, output towards load should be less than
90% of overall power generation.
T1000 Series UPS 1000-3000VA Installation and Operation Manual – 94086-001
1500VA
1000VA
1500VA
1000VA
900W
1350W
True Online, Double-Conversion
180-276V @ Full Load
Minimum: 120V @ 25%, 140V @ 50%, 160V @ 75% Load
45-65 Hz (auto-sensing)
4.7A
7.0A
208/220/240V (selectable from LCD panel)
< 5% THD at full non-linear load,
< 2.5% THD at full linear load
4.3A
6.5A
± 0.25 Hz (battery or free running mode)
106-120% 30 sec, 121-150% 10 sec
Internal Bypass (Automatic and Manual)
2000VA
2000VA
1800W
Single Phase
230V
0.97
9.4A
0.9
230V
± 2%
8.7A
50/60 Hz +/- 5%
Sine Wave
3:1
> 86%
3000VA
3000VA
2700W
14.1A
13A
40