Power Range:1000 Va (19" Rack-Mount Model, Lv, 1U & 2U) - Toshiba 1000 Series User Manual

Reliability in motion single phase 1000/1200 va
Hide thumbs Also See for 1000 Series:
Table of Contents

Advertisement

7.3 Power Range:1000 VA (19" Rack-mount model, LV, 1U & 2U)
General
Rated power:
Technology:
Input
Phase:
Bypass Voltage:
Input Voltage range:
Frequency:
Frequency window from main supply:
Synchronization window:
Input current:
Input Power factor:
Output
Output Voltage:
Voltage regulation:
Voltage distortion:
linear load:
Frequency regulation:
Dynamic response:
linear load:
Overload capacity:
Efficiency:
Environmental
Ambient temperature:
Recommended temperature: +15 °C to +25 °C
Storage temperature:
Cooling:
Humidity:
Audible noise:
1000 VA at power factor 0.7
On-line, double conversion topology with automatic
bypass
Single phase with ground
96VAC- 138VAC (user selectable)
80VAC- 144VAC
50/60 Hz Auto selection
45-65 Hz
± 3Hz
1000 VA 8.2A
0.97
100/110/115/120/127 VAC, selectable from LCD panel
± 2%
< 5% THD at full non-linear load, < 3% THD at full
± 0.25 Hz (battery or free running mode)
± 9 % max from 100% to 20 % or from 20% to 100 %
100-125% 1 min, 125-150% 10 sec
greater than 86%
+0 °C to +40 °C
-15 °C to +50 °C
Forced air-cooling
0-95%, non-condensing
< 45 db normal and battery mode (1000 ~1200 VA)
28