Normal Operation: Load Power Supplied By Each System Ups Inverter; Figure 3-1 Single Line Diagram - Normal Operation: Load Fed By Ups Inverter - Toshiba G2020 Series Installation And Operation Manual

480/480 v 500kva/750kva
Hide thumbs Also See for G2020 Series:
Table of Contents

Advertisement

3.2.1

Normal Operation: Load power supplied by each system UPS inverter

CB
Bypass
input
User
supplied
MCCB
CB
AC input
User
supplied
MCCB
Figure 3-1 Single Line Diagram – Normal Operation: Load fed by UPS inverter
During normal operation, the path through the UPS inverter is used to power the load.
In Figure 3-1 input AC power is converted to DC by the Converter. DC power is utilized to charge the UPS battery and to
provide power to the Inverter. The Inverter converts the DC power to clean AC power to supply the critical load.
The conversion-inversion process eliminates any voltage transients or fluctuations existing in the input power before it
reaches the critical load.
The power drawn by the critical load is equally shared between all UPS systems when multiple UPSs are in Parallel
Operation. (Refer to Figure 5-5 that shows a sample of Parallel Operation System Configuration.)
CAUTION
G2020 Series UPS Installation and Operation Manual – 94861-004
UPS Module
CONVERTER
/ CHARGER
CB1
Battery Cabinet
External
BATTERY
When in Parallel Operation, the rectifier inputs to all G9000 UPS Systems in the
Multi-Module System (MMS)-must be fed from a single source at all times including any
operation of Automatic Transfer Switches. All G9000 bypass inputs must also be fed from a
single source at all times (not necessarily the same source as the rectifier inputs).
52S
CB3
Static Transfer
Switch
INVERTER
52C
CB2
Output
Power Flow
Not in Use
9