Setting Of Two-Phase Counter - Hitachi HIDIC MICRO-EH Applications Manual

Table of Contents

Advertisement

8.3.2

Setting of Two-Phase Counter

The setting of the two-phase counters are stored in the special internal outputs (WRF072 to WRF07E).
(1)
Phase counting mode
Set the phase counting mode (0-3) in WRF06E. Please see the chapter 8.3.1 about phase counting mode.
WRF06F:
Phase counting mode
Figure 8.19 Special internal output for phase counting mode
(2)
Setting the on-preset value
Set the count value (the on-preset value) at which the counter output is turned on (or off). Any value in the range from 0
to FFFFH (0 to 65, 535) can be set. If the on-preset value is set to the same value as the off-preset value, or smaller than
the off-preset value, the counter will not perform any counting (see (4).).
WRF072:
On-preset value for two-phase counter
Figure 8.20 Special internal output for setting the on-preset value
(3)
Setting the off-preset value
Set the count value (the off-preset value) at which the counter output is turned off (or on). Any value in the range from 0
to FFFFH (0 to 65, 535) can be set. If the off-preset value is set to the same value as the on-preset value, or larger than the
on-preset value, the counter will not perform any counting (see (4).).
WRF076:
Off-preset value for two-phase counter
Figure 8.21 Special internal output for setting the off-preset value
(4)
Setting the counter preload
When preloading is used, the value to be preloaded should be set for each counter used. Any value in the range from 0 to
FFFFH (0 to 65, 535) can be set.
WRF07A:
Preload value for two-phase counter
Figure 8.22 Special internal output for setting the preload value
This special internal output becomes valid immediately after the setting.
(5)
Diagnostic error
If the on-preset and off-preset settings contain the same values for one or more counters when the PI/O function setting
flag (R7F5) is turned on, the corresponding bit in the abnormality display special internal output turns on and the
counters with abnormal settings do not perform any counting. (It does not count even if a counter input is entered.) In
addition, the setting abnormal flag (R7F7) turns on.
Bit:
15
14
WRF057:
a
Figure 8.23 Special internal output for input/output function abnormality
Bit
a
b
c
d
e
f
g
h
i
Two-phase counter 1 preset value abnormality
Chapter 8 High-speed counter, PWM / Pulse train output and Analogue I/O
13
12
11
10
9
Not used
Description of abnormality
Total pulse frequency abnormality
Pulse 4 frequency abnormality
Pulse 3 frequency abnormality
Pulse 2 frequency abnormality
Pulse 1 frequency abnormality
Counter 4 preset value abnormality
Counter 3 preset value abnormality
Counter 2 preset value abnormality
8-13
8
7
6
5
4
b
c
d
e
Related terminal
Y100 to Y103
Y103
Y102
Y101
Y100
X6
-
-
X0 to X3
3
2
1
0
f
g
h
I