Item number
Basic instructions-8
Ladder format
DIF n
DIF n
DIF n
DIF n
Instruction format
AND DIF n
OR DIF n
Usable I/O
n
Number
Function
Detects the rise of an input signal and retains the operation result only for one scan.
( ) indicates the display when the Ladder Editor is used.
Notes
DIF number may not be overlapped. (However, no error is generated even if overlapped numbers are used.)
DIF cannot use the b contact.
Program example
X00000
DIF0
Program description
Time chart
X00000
R123
1 scan time
Upon leading of X00000 on, R123 turns on only for one scan.
If b-contact is used for X00000, operation will be the same as the a-contact DFN operation.
Name
Condition code
R7F4
R7F3
R7F2
DER
ERR
SD
Number of steps
Condition
AND DIF n
OR DIF n
Bit
R,
TD, SS,
X
Y
M
CU, CT
WX WY
R123
5-18
Chapter 5 Instruction Specifications
Leading edge detection (AND DIF, OR DIF)
Processing time (µs)
R7F1
R7F0
Average
Maximum
V
C
1.0
Steps
3
4
Word
Double word
WR,
DR,
WM TC DX DY
DM
LD
X00000
AND
DIF0
OUT
R123
Remark
Other
0 to 511 (Decimal)