13.2 Checklist when Abnormality Occurred

If an error occurs in the MICRO-EH system, check the following items. If there are no problems in the following items,
contact our service department.
(a)
Power supply related items
Is the power voltage correct? (85 to 264 V AC)
Are there any warps in the power supply waveform?
Are there any excessive noises in the power supply?
Is power supplied for all basic and expansion units?
(b)
CPU related items
Are the initial settings (CPU initialization, I/O assignment, parameter settings, etc.) proper?
Are there any error codes that are output to the special internal output?
Is the RUN switch (or RUN terminal) in the proper location?
Are batteries mounted properly? Is the battery life still remaining? (23/28-point types only)
(c)
Input module related items
Is the input voltage within the specifications for the internal section?
Is there any noise or chattering in the input?
Do the I/O assignment numbers in the program match?
Is the wiring done properly?
(d)
Output module related items
Do the module and the load power supply type (DC/AC) match?
Do the load voltage and current match the specification of the output section?
Is there any noise or chattering in the output waveform?
Is the wiring done properly?
Do the I/O assignment numbers in the program match?
Are there any unintentional overlaps in the output numbers?
(e)
Wiring related items
Is the wiring between the expansions mixed up with other wires?
Are the power supply wiring and I/O cables separated?
Are there any foreign substances in the connector of the basic/expansion units?
Cautions
(a)
When returning the unit for repair, please notify us of the malfunctioning conditions in as much detail as possible
(including error codes, malfunctioning I/O bit number, will not turn on or off, etc.).
(b)
The tools and devices necessary for troubleshooting are briefly as follows:
Phillips/flathead drivers, digital multimeter, tester, oscilloscope (necessary depending on the case) etc.
13-5
Chapter 13 Troubleshooting