Hitachi HIDIC MICRO-EH Applications Manual page 72

Table of Contents

Advertisement

Item number
Basic instructions-13, 14
Ladder format
MCS n
MCS n
S
MCR n
MCR n
R
Instruction format
MCS n
MCR n
Usable I/O
n
Number
Function
Controls the input to the circuit sandwiched by the master control set (MCS n) and reset (MCR n).
(An AND operation is performed with respect to each input and MCS.)
The master control can be used up to eight layers.
( ) indicates the display when the Ladder Editor is used.
Notes
Always use the master control MCS and MCR in pairs.
Program example
X00000
MCS1
X00001
Y00100
MCR1
Program description
X00000
X00001
Y00100
When input X00000 is on, the circuits surrounded by MCS and MCR obeys input X00001, and output Y00100 turns on/off.
When input X00000 is off, the circuits surrounded by MCS and MCR are independent of input X00001, and output Y00100
turns off.
Name
Condition code
R7F4
R7F3
R7F2
DER
ERR
SD
Number of steps
Condition
MCS n
MCR n
Bit
R,
TD, SS,
X
Y
M
CU, CT
WX WY
LD
X00000
MCS1
LD
X00001
OUT
Y00100
MCR1
5-22
Chapter 5 Instruction Specifications
Set (start)/reset (cancel) master control (MCS, MCR)
Processing time (µs)
R7F1
R7F0
Average Maximum
V
C
0.7
Steps
3
0.7
2
Word
Double word
WR,
DR,
DL,
WM TC DX DY
DM
MCS0
MCS1
MCS2
Up to eight layers
MCR2
are allowed.
MCR1
MCR0
Remark
Upper case: MCS
Lower case: MCR
Other
0 to 49 (Decimal)