Hitachi HIDIC MICRO-EH Applications Manual page 166

Table of Contents

Advertisement

[3] Address of sending area :
Address number and address type are configured in 2 words as below.
s+4
s+5
[4] Reserved data size for data sending. : This is not actual data size but reserved size. Set it by "Word".
[5] Address of receiving area :
Address number and address type are configured in 2 words as below.
(Data format is as same as sending area.)
[6] Reserved data size for data receiving. : This is not actual data size but reserved size. Set it by "Word".
*1
[7]
Receiving data length :
If receiving data is found by data length, set this parameter by "Byte". The maximum size is 1,024 byte. If data is
more than 1,024 bytes or reserved area, TRNS command fails with DER="1".
*1
[8]
Start code :
If receiving data is found by start code, set this parameter.
b15
= 0 : Start code disabled.
= 1 : Start code enabled.
*1
[9]
End code :
If receiving data is found by end code, set this parameter.
b15
= 0 : End code disabled.
= 1 : End code enabled.
[10] Communication speed :
Baud rate
Value
300 bps
H0000
600 bps
H0001
1,200 bps
H0002
2,400 bps
H0003
4,800 bps
H0004
9,600 bps
H0005
19,200 bps
H0006
38,400 bps
H0007
57,600 bps
H0008
Type : WR → H000A
WM → H000C
I/O No.: H0000 -
b7
b0
Start code (H00 - HFF)
b7
b0
End code (H00 - HFF)
[11] Communication format
Format
7 bits, even parity, 2 stop
7 bits, odd parity, 2 stop
7 bits, even parity, 1 stop
7 bits, odd parity, 1 stop
8 bits, non parity, 2 stop
8 bits, non parity, 1 stop
8 bits, even parity, 1 stop
8 bits, odd parity, 1 stop
5-116
Chapter 5 Instruction specifications
Value
H0000
H0001
H0002
H0003
H0004
H0005
H0006
H0007