Item number
FUN instructions-4
Ladder format
FUN 82 (s)
* (SLREF (s))
Instruction format
FUN 82 (s)
* (SLREF (s))
Usable I/O
s
Number of points
s+1 and
Slot location number
beyond
Function
Performs refresh of the designated module for the number of points specified by s, starting with area s+1.
Refresh is performed by slot.
The slot location numbers stored in areas s+1 and subsequent are designated by the unit number and slot number.
The maximum number of points to be refreshed (n) is 64 points. The points exceeding 64 points are not refreshed.
If refresh processing is completed normally, DER is set to "0."
*
( ) indicates the display when the Ladder Editor is used.
Program example
R000
DIF0
Program description
Upon leading of R000, the two slots designated after WR0001 (unit 0, slot 0) and (unit 1, slot 0) are refreshed.
Name
Condition code
R7F4
R7F3
R7F2
DER
ERR
SD
Number of steps
Condition
Bit
R,
TD, SS,
X
Y
M
CU, CT
WX WY
Number of points to be refreshed
s
Refresh slot location number
s+1
s+2
Refresh slot location number
:
:
:
:
Refresh slot location number
s+n
WR0000 = H0002
WR0001 = H0000
WR0002 = H0010
FUN 82 (WR0000)
5-127
Chapter 5 Instruction Specifications
I/O Refresh (slot)
Processing time (µs)
R7F1
R7F0
Average Maximum
V
C
311
Steps
3
Word
Double word
WR,
DR,
WM TC DX DY
DM
n ≤ 64
Refresh slot location number is
designated by unit and slot number.
LD
AND
[
WR0000 = H0002
WR0001 = H0000
WR0002 = H0010
FUN82
]
Remark
Other
Designate the slot
location.
R000
DIF0
(WR0000)