Hitachi HIDIC MICRO-EH Applications Manual page 169

Table of Contents

Advertisement

Sample program
R7E3
WM103 = 0
WM104 = H000A
WM105 = H0000
WM106 = 16
WM107 = H000A
WM108 = H0100
WM109 = 256
WM10A = 0
WM10B = H8002
WM10C = H800D
WM10D = 6
WM10E = 0
WR10 = H0200
FUN 5 (WR10)
R7E3
WR100 = 9
WR101 = H0231
WR102 = H3830
WR103 = H3031
WR104 = H3338
WR105 = H0D00
Switch
DIF0
TRNS 0 (WY10, WM100, R0)
Description
TRNS 0 parameter and sent data are configured at 1
When the switch is ON, execution bit R0 is ON, and data is sent out from CPU port.
st
R7E3 : 1
scan ON
Timeout = 0
WR0
Reserve area for data sending :
16 words from WR0
WR100
Reserve area for data receiving :
256 words from WR100
Data receiving definition
Start code : H02, End code : H0D
Communication speed : 19.2k bps
Format : 7 bits, even, 2 stop
Port 2 configured as general purpose port.
Sent data : 9 bytes
Inverter (SJ300/L300P) command
FWD RUN for station No.18
02 31 38 30 30 31 33 38 0D
(STX 18 00 1 38 CR) [38=BCC]
R0
When the switch is ON, execution bit R0 is ON, and
S
data is sent out from CPU port.
R5
R5 enables data receiving from the other device.
S
st
scan by R7E3 contact.
5-119
Chapter 5 Instruction specifications

Hide quick links: