iMars grid-tied solar inverters
Setting item
Set power
Personal
LCD display
Input password
0000
set power
P-Lmt
Mode
LmtPower
P.Factor
Limit Mode
Invalid
Invalid
Auto
Manual
Limit Power
100%
Power Factor
Grid Tied Mode
Normal Mode
Power Factor 1.00
Input password
0000
Personal
MPP Start Volt
MPPT Volt
120V
The password is needed when enter into
the interface of "Set power". Get the
password from the supplier if necessary.
There are 3 submenus: ①P-Lmt Mode:
invalid (limited power function is
invalid),auto (special for single
phase) ,manual (set the limit of output
value manually); ② LmtPower: this
function is only valid when the P-Lmt
Mode is manual, the percentage is that
of the rated power and the setting range
is from 10% to 100%; ③Power factor:
includes normal model (default value
"1"), current advanced mode and current
hysteresis mode and the setting rage is
-0.9-0.99.
The password is needed when enter into
the personal interface. Get the password
from the supplier if necessary. It can set
MPPT starting voltage from 120V to
160V under the submenu of MPPT start
volt.